Quick Installation Guide
00825-0100-4697, Rev DB
September 2011
Rosemount 848T
17
NOTE:
NJ is valid with S001 and S002 Input Types
SPECIAL CONDITIONS OF SAFE USE:
1. The component must be housed in a suitable component certified enclosure that
provides a degree of protection of at least IP54 and meets the relevant material and
environmental requirements of IEC 60079-0: 2004 & IEC 60079-15: 2005.
2. Provision must be made, external to the component, to ensure the rated voltage of the
component supply is not exceeded by transient disturbances of more than 40%.
3. The electrical circuit is connected directly to earth; this must be taken into account when
installing the component.
Table 17. IECEx Approved Entity Parameters
Power/Bus Sensor
U
i
= 42.4 Vdc U
o
= 5 Vdc
C
i
= 0 I
o
= 2.5 mA
L
i
= 0 C
o
= 1000 F
L
o
= 1000 mH