Smart Wireless Gateway
April 2013
www.rosemount.com
Product certifications
Approved Manufacturing Locations
Rosemount Inc. – Chanhassen, Minnesota, USA
Emerson Process Management GmbH & Co. - Karlstein,
Germany
Emerson Process Management Asia Pacific Private Limited -
Singapore
Beijing Rosemount Far East Instrument Co., Limited - Beijing,
China
Telecommunication Compliance
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF spectrum.
Nearly every country requires this type of product certification.
Emerson is working with governmental agencies around the
world to supply fully compliant products and remove the risk of
violating country directives or laws governing wireless device
usage.
FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions. This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
Ordinary Location Certification for FM
As standard, the Gateway has been examined and tested to
determine that the design meets basic electrical, mechanical,
and fire protection requirements by FM, a nationally recognized
testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
North American Certifications
N5 FM Division 2, Non-Incendive
Certificate Number: 3028321
Nonincendive for Class I, Division 2, Groups A, B, C, and D.
Suitable for Class II, III, Division 1,
Groups E, F, and G; Indoors/outdoor locations;
Type 4X
Temperature Code: T4 (-40 °C < T
a
< 60 °C)
Canadian Standards Association (CSA)
N6 CSA Division 2, Non-Incendive
Certificate Number: 1849337
Suitable for Class I, Division 2, Groups A, B, C, and D.
Dust Ignition-proof for Class II, Groups E, F, and G;
Suitable for Class III Hazardous Locations.;
Install per Rosemount drawing 01420-1011.
Temperature Code: T4 (-40 °C < T
a
< 60 °C)
CSA Enclosure Type 4X
European Union Directive Information
The EC declaration of conformity for all applicable European
directives for this product can be found on the Rosemount
website
at www.rosemount.com. A hard copy may be obtained by
contacting your local sales representative.
European Certification
N1 ATEX Type n
Certificate Number: Baseefa 07ATEX0056X
ATEX Marking: II 3 G
Ex nA nL IIC T4 (-40 °C < T
a
< 60 °C)
Special condition for safe use (X):
The surface resistivity of the antenna is greater than one
gigaohm. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
The Apparatus is not capable of withstanding the 500V
insulation test required by Clause 9.4 of EN 60079-15:
2005. This must be taken into account when installing the
apparatus.
ND ATEX Dust
Certificate Number: Baseefa 07ATEX0057
ATEX Marking: II 3 G
Ex tD A 22 IP66 T135 (-40 °C < T
a
< 60 °C)
Maximum working Voltage = 28 V
N7 IECEx Type n
Certificate Number: IECEx BAS 07.0012X
Ex nA nL IIC T4 (-40 °C <
T
a
< 60 °C)
Maximum working voltage = 28 V
Special condition for safe use (X):
The surface resistivity of the antenna is greater than one
gigaohm. To avoid electrostatic charge build-up, it must
not be rubbed or cleaned with solvents or a dry cloth.
The Apparatus is not capable of withstanding the 500 V
insulation test required by Clause 9.4 of EN 60079-15:
2005. This must be taken into account when installing the
apparatus.
NF IECEx Dust
Certification Number: IECEx BAS 07.0013
Ex tD A22 IP66 T135 (-40 °C < T
a
< 60 °C)
Maximum working voltage = 28 V
Combinations of Certifications
KD Combination of N5, N6, and N1.